Nirvana Heat Pumps

FC SERIES

Ports to connect to on The Attendant:
HEATERS: H1- H5 on The Attendant or H1 – H2 on The Attendant Mini

Heat pumps, Heaters, and Chillers require a Water Temp Sensor wired to one of the Temp Sensor ports in order for the attendant to control the device.

These devices should only be powered directly from the power center or breaker panel. Do not run electricity through a relay as The Attendant will control the device to turn on/off by using the communication cable.

DO NOT Connect the remote wiring to a RS485 BUS terminal. It will cause irreversible damage to the circuit board.

Nirvana Heat pumps can only be controlled using legacy Dry Contact connections. This connection type allows The Attendant to control the heat pumps on/off state to manage the desired water temperature set point.

Low Voltage Wiring – Heat Only

Turn off power to the Nirvana Heat Pump.

Connect a two-wire 22 AWG conductor cable to the middle and right P/S terminals on the Nirvana Heat Pump control board located in the main electrical box.

Connect the other end of the cable to an open heater port on The Attendant. Refer to the diagram below.

Once wiring is completed, close up the electrical panel on the heat pump and restore power.

Programming Heat Pump – Heat Only

Press the Menu button for 5 seconds – ENTER TECH CODE will appear – Use the up arrow to go to 50 and press the Left Arrow to confirm:

The Tech Menu will now appear. Select External Control, and select ON with the UP
arrow and press the Left Arrow to confirm:

Press Menu 2 times and the machine will go back to the main display. In the Upper Right hand corner of the screen, EXT will appear to confirm that the External Control is active.

External Control can be activated in both POOL and SPA modes. Select the SPA mode in the main menu and confirm:

Once the SPA mode is selected, enter the maximum temperature that the
external control can require. The default maximum temperature is set to 104 degrees.

Programming The Attendant – Heat Only

Once in installer mode, go to the Devices tab and press the + button. From the Add Device screen, select Heat Pump.

Rename the heat pump, then choose Generic as the brand. Turn Off “Supports Cooling

Next, choose the port type and number for Heating. Adjust the minimum and maximum operating ambient temperature to match the heater specifications. Press Apply, then navigate to the Flows tab and assign your heater to the appropriate flow. When finished, press Apply and Save.

Your Nirvana Heat Pump is now wired, programmed, and ready to use!

Low Voltage Wiring – Heat/Cool Models

Turn off power to the Nirvana Heat Pump.

Connect a three-wire 22 AWG conductor cable to the left, middle, and right P/S terminals on the Nirvana Heat Pump control board located in the main electrical box. Note which Heater port you used for Pool(Cool) and Spa(Heat).

Connect the other end of the cable to an open heater port on The Attendant. Refer to the diagram below.

Once wiring is completed, close up the electrical panel on the heat pump and restore power.

Programming Heat Pump – Heat / Cool Models

Press the Menu button for 5 seconds – ENTER TECH CODE will appear – Use the up arrow to go to 50 and press the Left Arrow to confirm:

The Tech Menu will now appear. Select External Control, and select ON with the UP
arrow and press the Left Arrow to confirm:

Press Menu 2 times and the machine will go back to the main display. In the Upper Right hand corner of the screen, EXT will appear to confirm that the External Control is active.

External Control can be activated in both POOL and SPA modes. Select the desired mode in the main menu and confirm:

After selecting POOL or SPA mode, set the maximum temperature that the external control can request. In POOL mode, switch to COOL mode and adjust the temperature to the lowest safe setting. For SPA mode, set the maximum temperature to 104°F.

Programming The Attendant – Heat / Cool

Once in installer mode, go to the Devices tab and press the + button. From the Add Device screen, select Heat Pump.

Rename the heat pump, then choose Generic as the brand.

Next, choose the port type and number for Heating and Cooling. Adjust the minimum and maximum operating ambient temperature to match the heater specifications. Press Apply, then navigate to the Flows tab and assign your heater to the appropriate flow. When finished, press Apply and Save.

Your Nirvana Heat Pump is now wired, programmed, and ready to use!

Updated on December 6, 2024