Danfoss VACON X5 Variable Frequency Drive Pumps

Ports to connect to on The Attendant: BUS1 – BUS4
Ports to connect to on The Attendant Mini: BUS1 – BUS2

These devices should be powered directly from the power center or breaker panel. Do not connect this device to a relay. Do not connect any wires other than Data+ and Data- to any BUS ports on The Attendant.

You will need to use a standard CAT-5 or better cable with a custom RJ45 plug layout to connect your VFD to The Attendant.

Vacon X5 VFD RJ45 ConnectorAttendant Bus Port
Pin 3D+
Pin 6D-
Connector Pinout


Before you begin programming

Please note/record the following parameters values before starting programming. These are very important values that may already be configured for your pump and must be carried over into the Attendant configuration.

ParameterValue
301 (Min Frequency)Write down to configure min RPM
302 (Max Frequency)Write down to configure max RPM
303 (Preset Frequency 1)Write down to validate speed setting
304 (Preset Frequency 2)Write down to validate speed setting
509 (Rated Motor Volts)Write down to validate speed setting
510 (Rated Motor Volts)Write down to validate speed setting
511 (Rated Motor Rpm)Write down to configure max RPM
Record Parameters

Configuration

To control Vacon X5 VFD drives with The Attendant you must configure the VFD to enable communication using Modbus. Settings changes on the drive are performed using the two line display on the unit itself. The image below depicts the display and control buttons found on all Vacon X5 drives:

Entering Programming Mode

Hold down the SHIFT Key and press the PROG key to enter the Level 2 Programming mode. This mode provides access to all setting parameters.

Note: If you are missing certain parameter numbers when scrolling through the parameter list in programming mode one of the following may be an issue

1. Simply pressing the PROG key will take you into the Level 1 Programming mode that will not display all available parameters. Be sure to Hold down the SHIFT Key and press the PROG to enter LEVEL 2.

2. Some parameters are only accessible when the drive is in MACRO mode. To place the VFD into MACRO mode press and hold the PROG button for 3 seconds. You will see the screen read “Hold PROG for Macro Mode” confirming you are in macro mode.

Updating Parameter Values

ButtonUsage
Scroll to next parameter
Scroll to previous parameter
Edit the currently selected parameter value. Once you enter edit mode of a given parameter use

keys to change the value
Store selected parameter value
Programming Mode Keyboard

Configuration for Modbus (SIO) Control

Enable Modbus (SIO) Configuration Parameters

In order to make Modbus configuration parameters visible in the parameter list you must turn on the SIO Visible setting. To do so, enter Level 2 Programming mode (see instructions above) and update the register below:

ParameterValue
492 (SIO Visible)Yes
SIO Visible
Configure Modbus (SIO) Communication

Please be sure to set the following parameters on the VFD to enable Modbus operation:

ParameterValue
900 (SIO Protocol)RTU N81
901 (SIO Baud Rate)19200
902 (Comm Drop #) aka AddressSet the Unique Bus Identifier (Address) 1-247
Modbus Communication Parameters
Updated on April 9, 2024