Heaters and Chillers
The instructions below apply to Heat Pumps with a display that is pictured below:
Serial RS-485 Connection (Recommended)
The recommended connection mode for AquaCal heat pumps utilizes Serial RS-485 wiring. This connection enables The Attendant to switch between heating and cooling modes on heat pumps equipped with this capability.
- Turn off power to the heat pump and The Attendant
- Remove electrical access panel on the heat pump
- Route 22 gauge 2 conductor wire from The Attendant enclosure into the low voltage compartment of the heat pump.
- Connect wires to “Port B” of the control board in the heat pump
- Connect the other end of the wire to a Bus port on The Attendant
| Aquacal HeatPump | The Attendant |
| Pin A (Port B) | D+ |
| Pin B (Port B) | D- |
Once the wiring is completed you must put the heat pump into remote mode:
- Wake up the unit by swiping across the keypad
- Press Menu
- Use arrows to navigate to System and press Enter
- Use arrows to navigate to Advanced and press Enter
- Use arrows to navigate to External Control and press Enter
- Use arrows to pick External Control Mode and press Enter
- Use arrows to select SMART and press Enter.
- Use arrows to set the Local Address. Select 00, and press enter when done. [When configuring this device using the Poolside mobile app, you will enter 1 as the Bus Identifier.]
- Confirm OK to clear existing setups.
The heat pump should restart when the procedure is complete. You should see the following screen:
NOTE
If you see SMART COMM FAULT on your heat pump display there is an issue with your wiring or configuration on The Attendant
Troubleshooting
If the heat pump displays a “SMART COMM FAULT”:
- Confirm wiring – Confirm wires are oriented properly on the heat pump’s “Port B” of the control board.
- Deactivate power to heat pump and the Attendant.
- Remove the access panel on the heat pump.
- Reverse wires on “Port B”.
- Reinstall electrical access panel.
- Reactivate power to the Attendant.
- Reactivate power to the heat pump.